ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual page 123

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
12.34.58
Control of cooling additional stage – Temperature difference to basic stage
(x 0.1 °C)
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the control function parameter is set on either
"Cooling with additional stage" or "Heating and cooling with additional stages"
The setpoint temperature of the additional stage is define as a function of the current
setpoint temperature of the base stage and is expressed as a difference. The value
represents the setpoint value starting at which the additional stage will operate.
12.34.59
Control of cooling additional stage – Extended setting
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the control function parameter is set on either
"Cooling with additional stage" or "Heating and cooling with additional stages"
This parameter enables additional functions and communication objects, e.g. "additional
cooling stage".
12.34.60
Additional cooling stage – Control direction of control valve
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the control function parameter is set on either
"Cooling with additional stage" or "Heating and cooling with additional stages", only
available when the "Extended settings" parameter under "Control of cooling additional
stage" is set on "Yes".
The mode of the control value can be used to adapt the control value to de-energized
opened (normal) or de-energized closed (inverse) valves.
– Normal: Value 0 means "Valve closed".
– Inverse: Value 0 means "Valve open".
Input from 0 to 255
No
Yes
Normal
Inverse
122