Application "Staircase Lighting - ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Control input

Application "Staircase lighting"

12.28
With the "Staircase lighting" application, switching telegrams or value telegrams can be
provided with a light-on time. Depending on the parameterization, the application shows
different communication objects:
- a 1-bit object for input and output If an ON telegram is received via the "Input/Output"
object, the light-on time is started immediately. This can be a light-on time of 00:10 min
to 88:45 min, which is adjustable in 0.1 s steps. After expiration of the light-on time, the
"Input/Output" object sends an OFF telegram.
- two 1-bit objects for input and output
- and two 1-byte objects for input and output
If a telegram is received via the "Input" object, the light-on time is start immediately and a
telegram with the same value of the telegram received on the input is sent out on the
"Output" object. This can be a light-on time of 00:10 min to 88:45 min, which is adjustable
in 0.1 s steps. After expiration of the light-on time, the "Output" object sends out an OFF
telegram (1-bit) or a telegram with the value "0" (1-byte).
Via two additional communication objects, it is possible to specify the light-on time and
the switch-off prewarning time. The 2-byte values received are written to the memory of
the control element and are retained even after a bus power failure and subsequent return
of voltage.
12.28.1
Channel – Object type / number
Options
The "Object type/number" parameter sets the size and number of communication objects:
4 byte DPT 14.xxx
4 byte DPT 13.001
4 byte DPT 12.001
1 bit DPT 1.001
2 bit DPT 2.001
4 bit DPT 3.007
1 byte DPT 5.001
1 byte DPT 5.010
2 byte DPT 9.xxx
2 byte DPT 8.001
2 byte DPT 7.001
3 byte DPT 10.001
3 byte DPT 11.001
4 byte DPT 14.xxx
4 byte DPT 13.001
4 byte DPT 12.001
1 bit DPT 1.001
A 1 bit object for input and output
Two 1 bit objects for input and output
Two 1 byte objects for input and output
C, W
C, W
C, W
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, W
86