If the heating mode value specified by this parameter does not match the heating mode
value corresponding to the actual VRV air conditioner gateway protocol, the VRV
interface cannot control the heating mode of the VRV air conditioner
12.36.2
Operating mode – The code number of the cooling mode
Options
This parameter is used to specify the 1Byte value corresponding to the cooling mode.
Due to the different brands of the VRV air-conditioning-KNX protocol gateway to be
connected, the 1Byte value corresponding to the cooling mode used will be different.
Please refer to the actual VRV air-conditioning gateway protocol used Request to set the
corresponding value.
If the cooling mode value specified by this parameter does not match the cooling mode
value corresponding to the actual VRV air conditioner gateway protocol, the VRV
interface cannot control the cooling mode of the VRV air conditioner.
12.36.3
Operating mode – Activate fan only mode
Options
This parameter is used to select whether to turn on the fan mode for controlling the VRV
air conditioner. Please select this parameter according to whether the actual VRV air
conditioning system allows the fan mode to be turned on or not.
If you enable this parameter and the actual VRV air conditioning system does not allow
the fan mode to be turned on, the VRV interface cannot control the fan mode of the VRV
air conditioning
12.36.4
Operating mode – The code number of fan only mode
Options
Note: The following parameters will only be available when the "Fan only mode"
is activated. This parameter is used to specify the 1Byte value corresponding to the fan
only mode. Due to the different brands of the VRV air-conditioning-KNX protocol gateway
connected, the 1Byte value corresponding to the fan only mode used will be different.
Please refer to the actual VRV air-conditioning gateway protocol used.
Request to set the corresponding value.
If the fan only mode value specified by this parameter does not match the fan only mode
value corresponding to the actual VRV air conditioning gateway protocol, the VRV
interface cannot control the fan only mode of the VRV air conditioning.
Input from 0 - 255
Activate
Deactivate
Input from 0 - 255