Application "1-Button Light Scene Extension Unit With Memory Function - ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
Note": This parameter is only visible if the "Reaction at failing edge" parameter
is set on either "Value 2" or "Alternating Value1/Value2". The options are dependent on
the setting of the "Object type for failing edge" parameter.
Value 2 options are dependent on the setting of the "Object type for failing edge"
parameter.
– 1 bit: switching functions (e.g. On/Off, enable/blocked, true/untrue)
– 1 byte 0 - 100%: percentage values (0 = 0%, 255 = 100%)
– 1 byte 0 - 255: arbitrary values from 0 to 255
– 2-byte float: floating point value (physical values such as temperature or brightness) -
671088.64 to 671088.64
– 2-byte signed: arbitrary values from -32768 to +32767
– 2-byte unsigned: arbitrary values from 0 to 65,535
– 4-byte float: floating point value (physical values) -4000000 to 4000000
– 4-byte signed: arbitrary values from -2147483648 to 2147483647
– 4-byte unsigned: arbitrary values from 0 to 4294967295
12.11.9
Object no
Object name
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (rising edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)
Switching (failing edge)

Application "1-button light scene extension unit with memory function"

12.12
When a button is activated, a predefined light scene number is call backlight up. In each
case, the application makes a separate set of parameters and communication objects
st
available for the 1
and the 2nd button. The application makes it possible to call up a light
scene via one button side while the other button side can be assigned with a further
"button-oriented" function. The user has the option to trigger a light scene memory
command via a long actuation of the button.
Data type
1 bit DPT 1.001
1 byte DPT 5.001
1 byte DPT 5.010
2 byte DPT 9.xxx
2 byte DPT 8.001
2 byte DPT 7.001
4 byte DPT 14.xxx
4 byte DPT 13.001
4 byte DPT 12.001
1 bit DPT 1.001
1 byte DPT 5.001
1 byte DPT 5.010
2 byte DPT 9.xxx
2 byte DPT 8.001
2 byte DPT 7.001
4 byte DPT 14.xxx
4 byte DPT 13.001
4 byte DPT 12.001
Flags
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
C, W, T, U
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents