Temperature reading – Input of weighted temperature reading
Options
Note: This parameter is only available when the "Device function" parameter is
set on either "Single device" or "Master device" and the "Inputs of temperature reading"
parameter is set on "Weighted measurement".
Specifies the temperature reading inputs for the weighted measurement, in which the
calculated weighted average of the inputs is used as an input value for control
12.34.98
Temperature reading – Weighting of internal measurement (%)
Options
Note: This parameter is only available when the "Device function" parameter is
set on either "Single device" or "Master device" and the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement" or "Internal and 2x
external measurement".
Specifies the weighting of the internal measurement at a level between 0% and 100%.
12.34.99
Temperature reading – Weighting of external measurement (%)
Options
Note: This parameter is only available when the "Device function" parameter is
set on either "Single device" or "Master device" and the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement" or "Internal and 2x
external measurement".
Specifies the weighting of the external measurement at a level between 0% and 100%.
Internal and external measurement
2 x external measurement
Internal and 2x external measurement
Input from 0 to 100
Input from 0 to 100