HAT220A/HAT240A Automatic Transfer Switch Controller 1 SUMMARY HAT220A/HAT240A ATS controller has microprocessor as its core, can accurately detect 2 ways-3 phase, 2 ways-1 phase or 2ways-2phase voltage and also can make accurate judgment to conditions of abnormal voltage (loss of electricity, over or under voltage), control ATS to transfer after delay.
HAT220A/HAT240A Automatic Transfer Switch Controller connection terminals, small volume, compact structure with easy mounting and maintenance. 3 TECHNICAL SPECIFICATIONS Rated voltage and frequency input: 3-phase AC 380V 50/60Hz 3-phase 4 -wire (used for 220A controller) 1-phase AC 230V 50/60Hz Single-phase 2-wire (used for 240A controller)
HAT220A/HAT240A Automatic Transfer Switch Controller 4 FRONT PANEL OPERATION INSTRUCTION 5 FRONT PANEL OPERATION 5.1 DELAY ADJUSTMEN ♦ Adjusting potentiometer of “#I power supply normal delay” can set output delay after #I power supply normal. ♦ Adjusting potentiometer of “#II power supply normal delay” can set output delay after #II power supply normal.
HAT220A/HAT240A Automatic Transfer Switch Controller supply normal delay”; 2) Set “#II power supply abnormal delay” by adjusting potentiometer of “#II power supply normal delay”; 3) Set “Genset stop delay” by adjusting potentiometer of “Genset start delay”. b) After adjustment, press...
AC option Single-phase 2 3 phase 4 wire wire Note: In the above table of ten items, select “3-phase 4-wire” is used to HAT220A; select “single-phase 2-wire” when used HAT240A controller. 7 OPERATION CONTROL Auto/Manual operation, When controller in running, press key to transfer controller into Auto or Manual mode (Mode is indicated by lamps of Auto and Manual).
HAT220A/HAT240A Automatic Transfer Switch Controller simultaneously, then for no transfer priority. c) After adjustment, press key, when #I power supply indication lamp, automatic status indication lamp and #II power supply indication lamp illuminate simultaneously, the setting priority value will be saved successfully, then controller will work depending upon setting priority status.
HAT220A/HAT240A Automatic Transfer Switch Controller 10 CASE AND DIMENSIONS 11 FAULT FINDING Fault Symptom Possible Remedy Controller no operation Check connection wirings of controller Check ATS ATS is not working Check the connection wirings between the controller and the ATS...