Smartgen HES7120-PV User Manual page 50

Hybrid energy controller
Table of Contents

Advertisement

No.
Items
19
Reserved
20
Reserved
21
Inhibit Alarm Shutdown
22
Instrument Mode
23
Reserved
24
Reserved
25
Reserved
26
Reserved
27
Reserved
28
Remote Start
29
Reserved
30
Aux Manual Start
31
Reserved
32
Reserved
33
Simulate Stop Key
34
Simulate Manual Key
35
Reserved
36
Simulate Auto Key
37
Simulate Start Key
38
Simulate PV Key
39
Simulate PV Key
40
Simulate Busbar OK
41
Simulate Busbar Fail
42
Reserved
Busbar Divided 1 Power
43
Input
Busbar Divided 2 Power
44
Input
Busbar Divided 3 Power
45
Input
Busbar Divided 4 Power
46
Input
HES7120-PV Hybrid Engergy Controller
HES7120-PV HYBRID ENERGY CONTROLLER USER MANUAL
key and "Simulate Auto Mode" key are unavailable.
All shutdown alarms are inhibited except for emergency stop
(sometimes called War Mode or Override Mode)
All outputs are inhibited in this mode.
In the automatic mode, when the input is valid, PV can be
switched on automatically to generate power with load. When the
input is invalid, PV power generation can be automatically
stopped and opened.
When input is active in manual mode, PV generation will be
started automatically. When input is inactive, PV generation will
be stopped automatically.
Externally connecting a button to simulate key function on the
panel.
Externally connecting a button to simulate key function on the
panel.
In auto mode if input is active, then busbar is OK.
In auto mode if input is active, then busbar is abnormal.
If the busbar is divided into six inputs at most, it can be
considered as six gensets. When one input is effective and the
power of one genset is effective, all gensets will be switched on
and loaded. If several input ports are effective, several gensets
will be loaded. According to the configured busbar percentage N
power percentage, the accumulated sum is the minimum load
percentage of the current busbar to prevent reverse power
transmission to the bus bar, resulting in the bus reverse work.
2020-05-20
Description
Version
Page 50 of 59