6.2 CONTENTS AND SCOPES OF PARAMETERS

Items
No.
Busbar Setting
1
AC System
2
Rated Voltage
3
Rated Frequency
4
Normal Time
5
Abnormal Time
Voltage Transformer
6
(PT)
7
Over Voltage
8
Under Voltage
9
Over Frequency
10
Under Frequency
HES7120-PV Hybrid Engergy Controller
HES7120-PV HYBRID ENERGY CONTROLLER USER MANUAL
Table 12 Parameter Settings and Scope
Range
Default
(0-3)
0
(30-30000)V
230
(10.0-75.0)Hz
50.0
(0-3600)s
10
(0-3600)s
5
(0-1)
0
(30-30000)V
100
(30-1000)V
100
(0-1)
1
(0-200.0)%
120.0
(0-200.0)%
116.0
(0-3600)s
5
(0-4)
0
(0-1)
1
(0-200.0)%
80.0
(0-200.0)%
84.0
(0-3600)s
5
(0-4)
0
(0-1)
0
(0-200.0)%
114.0
(0-200.0)%
110.0
(0-3600)s
5
(0-4)
0
(0-1)
0
(0-200.0)%
90.0
2020-05-20
Description
0:3P4W;
1:3P3W;
2:2P3W;
3:1P2W。
Provide standard for judging busbar
over/under voltage or not; if voltage
transformer is applied, this value is the
primary voltage of transformer.
Provide standard for judging busbar
over/under frequency or not.
The time from busbar abnormal to
normal.
The time from busbar normal to
abnormal.
0: Disabled; 1: Enabled
Primary voltage
Secondary voltage
0: Disabled; 1: Enabled
The setting value is rated voltage
percentage
The return value is rated voltage
percentage
Delay value
Action type
0: Disabled; 1: Enabled
The setting value is rated voltage
percentage
The return value is rated voltage
percentage
Delay value
Action type
0: Disabled; 1: Enabled
The setting value is rated frequency
percentage
The return value is rated frequency
percentage
Delay value
Action type
0: Disabled; 1: Enabled
The setting value is rated frequency
percentage
Version