Smartgen HES7120-PV User Manual page 48

Hybrid energy controller
Table of Contents

Advertisement

No.
126
Reserved
127
Reserved
128
Shutdown Mode of System
129
Manual Mode of System
130
Reserved
131
Automatic Mode of System
132
PV Power Load Indication
133-
Reserved
239
6.3.1 CUSTOMIZED COMBINATION OUTPUT
Defined combination output is composed by 3 parts, condition output S1 or S2 and condition
output S3.
S1 or S2 is TRUE, while S3 is TRUE, defined combination output is outputting;
S1 and S2 are FALSE, or S3 is FALSE, defined combination output is not outputting.
NOTE: S1, S2, S3 can be set as any contents except for "defined combination output" in the output setting.
NOTE: 3 parts of defined combination output (S1, S2, and S3) couldn't include or recursively include themselves.
Example,
Contents of probably condition output S1: output port 1 is active;
Close when probably condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of probably condition output S2, output port 2 is active;
Close when probably condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of probably condition output S3: output port 3 is active;
Close when probably condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination output is outputting; If input
port 3 inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined combination output
is not outputting.
HES7120-PV Hybrid Engergy Controller
HES7120-PV HYBRID ENERGY CONTROLLER USER MANUAL
Type
Activated when the system is in shutdown mode.
Activated when the system is in manual mode.
Activated when the system is in automatic mode.
Activated when PV power load indicated.
Description