Smartgen HES7120-PV User Manual page 32

Hybrid energy controller
Table of Contents

Advertisement

Items
No.
11
Loss of Phase
12
Reverse Phase
Transformation Ratio
13
of
Current
Transformer
Selection of Busbar
14
Active Power Input
Selection of Busbar
15
Reactive Power Input
16
Rated Active Power
Rated
Reactive
17
Power
18
Reverse Power
19
Over Power
20
Unbalanced Voltage
Timer Setting
1
Start Delay
HES7120-PV Hybrid Engergy Controller
HES7120-PV HYBRID ENERGY CONTROLLER USER MANUAL
Range
Default
(0-200.0)%
94.0
(0-3600)s
5
(0-4)
0
(0-1)
1
(0-1)
1
(5-6000)/5
500
(0-6)
0
(0-6)
0
(0-6000)kW
276
(0-6000)kW
210
(0-1)
0
(0-200.0)%
10.0
(0-200.0)%
5.0
(0-3600)s
5
(0-4)
0
(0-1)
0
(0-200.0)%
110.0
(0-200.0)%
105.0
(0-3600)s
5
(0-4)
0
(0-1)
0
(0-200.0)%
10.0
(0-200.0)%
5.0
(0-3600)s
5
(0-4)
0
(0-3600)s
1
2020-05-20
Description
The return value is rated frequency
percentage
Delay value
Action type
0: Disabled; 1: Enabled
Transformation ratio of external current
transformer
0: current transformer; 1: sensor 1;
2: sensor 2; 3: Sensor 3; 4: sensor 4;
5: sensor 5; 6: Communication
provide a reference for the judgment of
bus reverse power over power or
active power percentage.
provide a reference for the judgment of
busbar reactive power percentage.
0: Disabled; 1: Enabled
The setting value is rated active power
percentage
The return value is rated active power
percentage
Delay value
Action type
0: Disabled; 1: Enabled
The setting value is rated active power
percentage
The return value is rated active power
percentage
Delay value
Action type
0: Disabled; 1: Enabled
The
setting
value is unbalanced
voltage percentage
The return value is unbalanced voltage
percentage
Delay value
Action type
Time
between
busbar normal or
remote start signal is active and genset
start.
Version
Page 32 of 59