Signaling Line Circuit (Slc); Notification Appliance Circuits & Releasing Circuits; Output Relays; Four-Wire Smoke Detector Power - Honeywell XLS140 Installation Manual

Fire alarm control panel
Table of Contents

Advertisement

Electrical Specifications

Signaling Line Circuit (SLC)

Item
Voltage
Maximum length
Maximum current
Maximum resistance
Notification Appliance Circuits & Releasing Circuits
Item
Max. wiring voltage drop
Nominal operating voltage
Current for all external
devices connected to the
control panel's power supply
Optional ACPS-2406
Optional APS-6R
Maximum signaling current/
circuit per NAC
End-of-Line Resistors
(ELRs)

Output Relays

Output relays for Alarm, Trouble, Supervisory, and Security are available on power supply
terminals TB8, TB9, TB10, and TB11 respectively.
Contact ratings: 2.0 A @ 30 VDC (resistive)

Four-wire Smoke Detector Power

Control Panel terminals TB7 RESET (+) and (–) supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
Nominal voltage: 24 VDC
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible 24 VDC detectors.

Power Output

Control Panel terminals TB7 NONRST (+) and (–) supply one (1) power-limited circuit available
to power external devices, such as notification appliances and annunciators.
Nominal voltage: 24 VDC
Maximum rated current: 1.25 A DC
Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible devices and notification appliances.
NOTE: The Control Panel provides a total of 6.0 A of power in alarm (3 A in standby), shared by
all internal circuitry and external provisions (24 V resettable and non-resettable). For power
requirements, refer to the power supply calculation tables in Appendix A.
78
Value
24 VDC nominal, 27.6 VDC maximum
12,500 ft. (3810 m) per channel (NFPA Style 4) or 10,000 ft. (3048 m) total
loop or circuit length (NFPA Style 6 and 7)
Note: Refer to Appendix B.2 "Wire Requirements" for limitations.
400 mA peak, 200 mA average (max short circuit; circuit will shut down until
short is fixed)
50 ohms (supervised and power-limited)
Value
2 VDC (except CMX which is 1.2 VDC)
24 VDC
6.0 A in alarm (3 A continuous)
Total 6 A in alarm (5 A continuous)
Total 6 A in alarm (4 A continuous)
2.5 A
Note: Some devices have maximum draws less than this; refer to the device's
documentation.
Control Panel NACs (TB3, TB4, TB5, TB6): 2.2K, 1/2 watt
ICM-4RK, ICE-4, VCM-4RK, VCE-4, and DCM-4RK: 4.7K,
1/2 watt (2 watts on 70 Vrms audio)
XP6-C, XLS-CM-N/TC810N1013 Modules: 47K, 1/2 watt
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005