IFP-2000 Installation Manual
3.3
Electrical Specifications
Terminal Label
B
AC input (hot)
G
Earth ground
W
AC input (neutral)
X
*I/O 1
Flexput™ Circuits
O
X
*I/O 2
Flexput™ Circuits
O
X
*I/O 3
Flexput™ Circuits
O
X
*I/O 4
Flexput™ Circuits
O
X
*I/O 5
Flexput™ Circuits
O
X
*I/O 6
Flexput™ Circuits
O
X
*I/O 5
Flexput™ Circuits
O
X
*I/O 8
Flexput™ Circuits
O
B
SBUS communication
A
SBUS1 OUT
+
SBUS power
-
*
Regulated for NAC circuits
*
Special application when used for releasing or auxiliary power circuits.
3-2
Description
Voltage
120/240 VAC,
50/60 Hz
N/A
120/240 VAC,
50/60 Hz
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
5 VDC
24 VDC
firealarmresources.com
Earth Ground
Rating
Current
5A for the IFP-2000,
2.5A for the IFP-2000HV
N/A
5A for the IFP-2000,
2.5A for the IFP-2000HV
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
3.0 Amp Notification and
Aux power Circuits
100 mA for initiation
circuits
100 mA
1.0 A
Faults
N/A
N/A
N/A
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
151430