b. Set Summer Time Start/End. The following is
displayed:
Summer Time START Date:
0=None/1=Last Sunday March/2=Define: 0
Select the required option. If you press the '2'
pushbutton the following is displayed:
Month : n
Use the numeric pushbuttons to enter the month and
press
Date : n
Use the numeric pushbuttons to enter the date and
press
Summer Time END Date:
0=None/1=Last Sunday October/2=Define: 0
Select the required option. If you press the '2'
pushbutton, enter the month and date as described
above for the START date. To complete the process,
press

4.12 Select Day or Night Mode

To select Day Mode and Night Mode press the 8
pushbutton. If this function is configured the following
menu is displayed:
Select Day/Night Mode:
Passcode Access 2? _
Enter the passcode and press pushbutton
Select Day/Night Mode:
0=NIGHT MODE/1=DAY MODE: 0
Select the appropriate option. The LCD returns to the
Top Level display. If Day Mode was selected the
DISABLEMENT and DAY MODE LEDs light and 'System
in DAY mode' is displayed on the LCD.
If an alarm occurs during DAY MODE, the DAY MODE
LED flashes and the first investigation time begins,
delaying activation of the remote fire outputs. Press
ACCEPT during this time to extend the delay (second
investigation time minus the expired first time). Press
EVACUATE to activate remote fire outputs immediately.

4.13 Set Language

This function selects the language displayed on the LCD.
From the Top Level menu, press the 7 pushbutton to
display the language selection menu. Select the
appropriate option.
Set Language: n
0=English/1=Español/2=Islenka: 0
The languages shown are examples only.