Group; 1: Edit Group; Edit Group Name; Edit Group Properties - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

9.4 Group

An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify program-
ming because you only have to program the output characteristics that are common to all of the group points once, instead of program-
ming each individual point. Once you have defined the characteristics of output groups, you can assign each point to the appropriate
group. All valid output points are assigned to only one output group. Unused points are not assigned to any output group. Up to 999 out-
put groups can be defined.
9.4.1 Edit Group
In the edit group option you can program the name of an output group (Section Edit Group Name) and change the properties of that
group.
To edit a group, follow these steps:
1.
Enter the installer code. The panel will automatically go the main menu.
2.
Select 7 for Program Menu.
3.
Press 3 to enter group menu.
4.
Press 1 to edit group.
5.
Enter the number of the group you wish to edit, then press ENTER.

Edit Group Name

6.
To edit the group name, press 1.
You can use words to display a descriptive name for a group.
Appendix B
NOTE: See

Edit Group Properties

7.
To edit the group properties, Press 2 from the edit group menu.
NOTE: These settings only apply to non-voice groups
Select Y for voice group and N for non-voice group.
Select / Dynamic Activation switch number: used when the group is defined as a voice group; or as a non-voice group where
Dynamic Activation is used. This option links the output group with a voice select switch on a VCM, RVM, or switch expander for
dynamic activation/deactivation. See the Section Activating Output Groups Dynamically for more information.
Template Override is shown when set to Yes.
Dynamic Activation -Is shown if a non-voice group is assigned to a Select/Dynamic Activation switch number
Dynamic Activation / Template Override Cadence. (This is shown when the Template override is set to Yes or if a non-voice group
is assigned a Select/Dynamic Activation switch number): this setting sets the cadence of the non-voice group mapped to voice
select switch when activated using dynamic activation or by a template. See Sections Activating Output Groups Dynamically and
Section 9.5 for more information..
Defining Output Group Type
Each output group is defined as either a voice output group or a non-voice output group. Output points that are
audio circuits (all circuits on the EVS-50W, EVS-125W, EVS-100W, EVS-INT50W and EVS-CE4) can only be assigned to voice output
groups. Output points that are non-voice circuits (all other points and circuits that are on all modules except the EVS-50W, EVS-125W,
EVS-100W, EVS-INT50W and EVS-CE4) are assigned to non-voice output groups.
118
for editing names.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents