Table of Contents

Advertisement

234 Technical data
ACH580-
Input
01-
rating
current
I 1
A
04A1-4
3.4
05A7-4
4.8
07A3-4
6.0
09A5-4
7.6
12A7-4
11.0
018A-4
14.0
026A-4
21.0
033A-4
27.0
039A-4
34.0
046A-4
40.0
062A-4
52
062A-4
52
073A-4
65
073A-4
65
089A-4
77
088A-4
77
106A-4
96
145A-4
124
169A-4
156
206A-4
180
246A-4
240
293A-4
260
363A-4
361
430A-4
414
1)
Continuous current, no overloadability
See definitions and notes in section

Definitions

U n
Nominal output voltage of the drive. For input voltage range [U 1 , see section
Electrical power network specification (page
60 Hz for UL (NEC) ratings.
I 1
Nominal input current. Continuous rms input current (for dimensioning cables and
fuses).
I max
Maximum output current. Available for two seconds at start.
Max.
Nominal use
I max
I Ld
A
A
kW
5.4
3.5
1.5
6.1
4.8
2.2
7.2
6.0
3.0
8.6
7.6
4.0
13.7
12.0
5.5
19.8
14.0
7.5
25.2
23.0
11.0
37.8
27.0
15.0
48.6
34.0
18.5
61.2
44.0
22.0
76
52
30
72
52
30
94
65
37
94
65
37
117
77
45
122
77
45
148
96
55
178
124
75
247
156
90
287
180
110
350
240
132
418
260
160
542
361
200
542
414
250
Definitions (page 234)
Output ratings
Heavy-duty use
P Ld
I Hd
hp
A
2.0
3.0
3.0
3.4
3.0
4.0
5.0
4.8
7.5
7.6
10.0
11.0
15.0
14.0
20.0
21.0
25.0
27.0
30.0
34.0
40
40
40
40
50
52
50
52
60
65
60
65
75
77
100
96
125
124
150
156
200
180
240 1)
200
300
302
361 2)
350
286). 50 Hz for IEC ratings and
Frame
P Hd
kW
hp
1.1
1.5
R1
1.5
2.0
R1
2.2
3.0
R1
3.0
3.0
R1
4.0
5.0
R1
5.5
7.5
R2
7.5
10.0
R2
11.0
15.0
R3
15.0
20.0
R3
18.5
25.0
R3
22
30
R4
22
30
R4 v2
30
40
R4
30
40
R4 v2
37
50
R4 v2
37
50
R5
45
60
R5
55
75
R6
75
100
R7
90
125
R7
110
150
R8
132
150
R8
160
250
R9
200
300
R9

Advertisement

Table of Contents
loading

Table of Contents