Relay cable

The cable type with braided metallic shield (for example ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.

Control panel to drive cable

Use EIA-485, Cat 5e (or better) cable with male RJ-45 connectors. The maximum length
of the cable is 100 m (328 ft).

PC tool cable

Connect the Drive Composer PC tool to the drive through the USB port of the control
panel. Use a USB Type A (PC) - Type Mini-B (control panel) cable. The maximum length
of the cable is 3 m (9.8 ft).

FPBA-01 PROFIBUS DP adapter module connectors

Frames R1...R3: The following connector types have been tested to fit in the tight space
for option slot 1.
Phoenix Contact SUBCON-PLUS-PROFIB/PG/SC2, part number 2708245. Lead
the cable through the control cable hole on the right in the entry plate (1).
Siemens, part number 6GK1 500 0EA02. Lead the cable through the middle control
cable hole in the entry plate (2).

Routing the cables

General guidelines – IEC
Route the motor cable away from other cables. Motor cables of several drives can
be run in parallel installed next to each other.
Install the motor cable, input power cable and control cables on separate trays.
Avoid long parallel runs of motor cables with other cables.
Guidelines for planning the electrical installation 103