Optional Heatshift; Remove Convection Baffle; Install Heatshift Take-Off Collars - Valor H6 Installation Manual

Direct vent zero clearance gas fireplace
Table of Contents

Advertisement

Preparation
ONLY If You Are Installing HeatShift
Perform the following steps and see Appendix D -
HeatShift System on page 79–98 for more details
regarding HeatShift planning and installation.
Remove Convection Baffl e
To be eff ective, the HeatShift system requires that an
internal convection baffl e located above the fi rebox
inside the appliance case be removed to allow the hot
air fl ow to convect upwards into ducts installed on the
fi replace.
Remove the convection baffl e from the appliance. It is
held in place by 4 screws located right behind the upper
edge of the fi replace opening. Recycle this panel as it is
no longer needed.
Appliance top panel shown transparent for clarity
C o
n v
e c t
i o n
Remove convection baffl e—1400M
 WARNING
The H6 fireplace requires the removal
of the internal convection baffle for the
HeatShift system to function properly—
read instructions carefully!
40
B a
ffl e

Optional HeatShift

Install HeatShift Take-Off Collars
1. Remove the four cover plates on top of the appli-
ance case (6 screws each).
2. Install the four take-off collars on the holes on top
of the appliance's case (6 screws each).
 WARNING
A l l F O U R ( 4 ) t a k e o f f s M U S T B E
C O N N E C T E D T O P L E N U M ( S ) .