Chapter 2 Specifications; General Specifications - Mitsubishi Electric CC-Link IE Field NZ2GF12A-60IOLH8 User Manual

Network waterproof remote io-link module
Table of Contents

Advertisement

2
SPECIFICATIONS
This chapter describes the specifications of the IO-Link module.
2.1

General Specifications

Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance
Shock resistance
Operating atmosphere
*2
Operating altitude
Installation location
*3
Overvoltage category
*4
Pollution degree
Equipment class
*1 The product specifications are satisfied only when all of waterproof plugs and waterproof caps are installed with the recommended
connectable devices and all screws are tightened with an appropriate torque.
*2 Do not use or store the IO-Link module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause
malfunction. When using the IO-Link module under pressure, please consult your local Mitsubishi representative.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category  applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for the
equipment with the rated voltage of 300V or less is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
To use the IO-Link module complying with the EMC Directive, refer to "EMC and Low Voltage Directives" in
this manual. ( Page 146 EMC and Low Voltage Directives)
2 SPECIFICATIONS
20
2.1 General Specifications
Specifications
0 to 55 (0 to 40 for UL listed)
-25 to 75
*1
Conforming to IP67
5 to 95%RH, non-condensing
Compliant with JIS
B 3502 and IEC
61131-2
Under intermittent
vibration
Under continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
No corrosive gases
0 to 2000m
Inside/outside a control panel
 or less
2 or less
Class 
Frequency
Constant
acceleration
5 to 8.4Hz
8.4 to 150Hz
9.8m/
5 to 8.4Hz
8.4 to 150Hz
4.9m/
Half amplitude
Number of sweeps
3.5mm
X, Y, Z
10 times each in X,
Y, and Z directions
1.75mm