2
SPECIFICATIONS
This chapter describes the specifications of the IO-Link module.
2.1
General Specifications
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance
Shock resistance
Operating atmosphere
*2
Operating altitude
Installation location
*3
Overvoltage category
*4
Pollution degree
Equipment class
*1 The product specifications are satisfied only when all of waterproof plugs and waterproof caps are installed with the recommended
connectable devices and all screws are tightened with an appropriate torque.
*2 Do not use or store the IO-Link module under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause
malfunction. When using the IO-Link module under pressure, please consult your local Mitsubishi representative.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for the
equipment with the rated voltage of 300V or less is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
To use the IO-Link module complying with the EMC Directive, refer to "EMC and Low Voltage Directives" in
this manual. ( Page 146 EMC and Low Voltage Directives)
2 SPECIFICATIONS
20
2.1 General Specifications
Specifications
0 to 55 (0 to 40 for UL listed)
-25 to 75
*1
Conforming to IP67
5 to 95%RH, non-condensing
Compliant with JIS
B 3502 and IEC
61131-2
Under intermittent
vibration
Under continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
No corrosive gases
0 to 2000m
Inside/outside a control panel
or less
2 or less
Class
Frequency
Constant
acceleration
5 to 8.4Hz
8.4 to 150Hz
9.8m/
5 to 8.4Hz
8.4 to 150Hz
4.9m/
Half amplitude
Number of sweeps
3.5mm
X, Y, Z
10 times each in X,
Y, and Z directions
1.75mm