7.2

Parameter Setting

Parameter setting of the safety remote I/O module can be done with the following methods.
• Slave station parameter automatic setting (Page 59 Slave station parameter automatic setting)
• Parameter processing of slave station (Page 62 Parameter processing of slave station)
Even if the safety remote I/O module is replaced due to a failure of the safety remote I/O module when parameters are set
with slave station parameter automatic setting, the parameters of the safety remote I/O module are automatically set via the
master station.
This saves one the trouble of having to newly set parameters.
Window
Setting item list
Item
Station parameter
Safety setting
Link speed setting
Setting details
Transmission interval
Set the transmission interval
monitoring time
monitoring time for safety data.
I/O LED indication
Set whether the input and output
setting at error
points where an error is detected
occurrence
is indicated with an LED.
Safety approval code
Set a safety approval code that
identifies the individual safety
remote I/O module.
Set a communication speed with
which the safety remote I/O
module links up.
Setting range
Reference
4 to 1000(ms)
Page 143 Transmission
interval monitoring time
0: No indication of error
Page 143 I/O LED
point
indication setting at
1: Indication of error
error occurrence
point
0x00000000 to
Page 144 Safety
0xFFFFFFFF
approval code
0: 1Gbps
Page 144
1: 100Mbps
Communication speed
2: automatic
setting
7 SETTINGS
7.2 Parameter Setting
7
57