Appendix 3
The transmission delay time of the IO-Link module is a total of the following times.
• CPU module sequence scan time
• CC-Link IE Field Network link scan time
• IO-Link module internal processing cycle
• IO-Link cycle time
For details on the CPU module sequence scan time, refer to the following.
User's manual for the CPU module used
For details on the CC-Link IE Field Network link scan time, refer to the following.
 User's manual for the master/local module used
IO-Link module internal processing cycle
The IO-Link module internal processing cycle is fixed to 2ms.
IO-Link cycle time
The IO-Link cycle time is determined by the IO-Link device connected.
For details, refer to the manual of the IO-Link device.
Ex.
The transmission delay time with an IO-Link device connected to channel 1 of the IO-Link module is as follows.
Item
CPU module sequence scan time
CC-Link IE Field Network link scan time
IO-Link module internal processing cycle
IO-Link cycle time
Transmission delay time = 0.3 + 0.19 + 2 + 0.4 = 2.89ms
Processing Time
Condition
High-speed mode, single station, RX/RY: 32 points, RWw/RWr: 4 points
Fixed to 2ms.
Processing
time
0.3ms
0.19ms
2ms
0.4ms
APPX

Appendix 3 Processing Time

A
145