Mitsubishi Electric CC-Link IE Field NZ2GF12A-60IOLH8 User Manual page 56

Network waterproof remote io-link module
Table of Contents

Advertisement

Changing the parameter without changing the network configuration
To change only the created module parameter of the slave station without changing the network configuration, set the
parameter in the following procedure.
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Module Parameter]  [Basic Settings]
 [Network Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module  [CC IE Field Configuration]  [Online]  [Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Parameter Read".
4.
Click the [Execute] button and the following window is displayed.
5.
Click the [Yes] button.
6.
The parameters are read from the IO-Link module.
7.
Set "Method selection" to "Parameter Write".
6 Parameter Setting
54
6.3 Changing the IO-Link Module Parameters