HEURISTIC CONTROL POWER

It is useful to be able to limit the delivery of total power to the loads in order to avoid input peaks from the single-phase
power line.
This condition occurs during switch-on phases when the machine is cold; the demand for heating power is 100%
until temperatures near the setpoint are reached. It is also useful to avoid simultaneity of conduction when there is ON-OFF
modulation for temperature maintenance.
The cycle time must be identical for all zones; the power percentage for each zone is limited to that necessary to
maintain current within set limits.
This function acts by enabling the control to search for the most appropriate input combinations.
Example 1:
3 loads 380V- 32 A (zone 1), 16 A (zone 2), 25 A (zone 3), 40 A (maximum current is 73 A in case of simultaneity of conduction).
Current limit I.HEU=50 A.
The following combinations of conduction are possible:
(to define the number of combinations, remember that the combinations without repetitions are = n! / (k!*(n-k)!) )
I1+I2 = 48 A
I1+I3 = 57 A
I2+I3 = 41 A
I1+I2+I3 = 73 A
The combinations corresponding to current values below the limit value are:
I1+I2 = 48 A
I2+I3 = 41 A
The one with lower current is given by zone 2 and zone 3
In the single cycle time for the enabled zones, the delivery of power may be reduced to respect the maximum current limit.
The time distribution for activation of the zones is calculated at the start of each cycle:
Ptot = P1+ P2(se P2>P3) + P3(se P3>P2) Simultaneity is allowed for zones 2 and 3.
Se P1= 100%, P2= 100%, P3= 100%
Ptot=200%; since Ptot>100%, the conduction time of the zone x is obtained by Px * (100/Ptot)
P1,2,3 delivered = 100%*0.5 = 50%
If P1= 100%, P2= 50%, P3= 0%
Ptot=150%; since Ptot>100%, the conduction time of the zone x is obtained Px * (100/Ptot)
P1 delivered = 100%*0.66 = 67%
P2 delivered = 50%*0.66 = 33%
P3 delivered = 0%*0.66
80997D_MSW_GFW_400-600_04-2021_ENG
= 0%
ON Zone 1
ON Zone 2 / 3
Cycle time
ON Zone 1
Cycle time
ON Zone 2
63