Power Fault ALARMS (SSR_SHORT, NO_VOLTAGE and NO_CURRENT)
660*
R/W
hd.2
661
R/W
dg.t
662*
R/W
dg.f
Reset
SSR_SHORT /
105*
R/W
NO_VOLTAGE /
bit
NO_CURRENT
alarms
Read state
State of alarm
96*
SSR_SHORT
bit
phase 1
State of alarm
97
SSR_SHORT
bit
phase 2
State of alarm
98
SSR_SHORT
bit
phase 3
State of alarm
99*
NO_VOLTAGE
bit
phase 1
State of alarm
100
NO_VOLTAGE
bit
phase 2
State of alarm
101
NO_VOLTAGE
bit
phase 3
State of alarm
102*
NO_CURRENT
bit
phase 1
State of alarm
103
NO_CURRENT
bit
phase 2
80997D_MSW_GFW_400-600_04-2021_ENG
Enable POWER_FAULT
alarms
Frequenza di aggiornamento
SSR_SHORT Attesa (in secondi)
di attivazione dell'allarme
Filtro a tempo per gli allarmi
NO_VOLTAGE e NO_CURRENT
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
OFF = Alarm OFF
R
ON = Alarm ON
Table of Power Fault alarms
SSR _SHORT
NO_ VOLTAGE NO_ CURRENT
0
1
X
X
2
X
3
X
4
5
X
6
X
7
X
X
8
9
X
10
X
11
X
X
12
13
X
14
X
15
X
X
+ 32 alarms with memory
+ 136 enables partial load mode (128+8) for three-phase delta
configuration without neutral, with or without transformer Y/Y or Δ /Δ)
+ 264 enables partial load mode (256+8) for three-phase delta
configuration without neutral, with or without transformer Δ/Y or Y/Δ)
+512 enable current polarity control (inductive loads only)
1...999 sec.
Set a value not less than
0...99 sec.
cycle time
with 3-phase load
with 3-phase load
with 3-phase load
with 3-phase load
with 3-phase load
0
0
0
Zone 1
Zone 2
Zone 3
X
X
X
X
X
X
X
X
10
10
10
10
Zone 1
Zone 2
Zone 3