ALLOCATION OF REFERENCE SIGNALS

160*
rL.1
163*
rL.2
NOTE: Parameters rL.1, ..., rL.6 for each zone can be consi-
dered as internal states.
Ex.: To assign alarm AL1 to physical output OUT5, assign rL.1-
Zone1=2 (AL1-alarm 1) and than assign parameter out.5=1
(rL.1-Zone1)
80997D_MSW_GFW_400-600_04-2021_ENG
R/W
Allocation of reference signal
R/W
Allocation of reference signal
Table of reference signals
Function
0
Ou.P (control output)
2
AL1 - alarm 1
3
AL2 - alarm 2
4
AL3 - alarm 3
AL.HB or POWER_FAULT with alarm
5
HB (TA1 or TA2 or TA3)
7
IN1 - repetition of logic input INDIG1
8
AL4 - alarm 4
9
AL1 or AL2
10 AL1 or AL2 or AL3
11 AL1 or AL2 or AL3 or AL4
12 AL1 and AL2
13 AL1 and AL2 and AL3
14 AL1 and AL2 and AL3 and AL4
AL1 or AL.HB or POWER_FAULT with
15
HB alarm (TA1 or TA2 or TA3)
AL1 or AL2 or (AL.HB or POWER_
16
FAULT) with HB alarm (TA1 or TA2 or
TA3)
AL1 and (AL.HB or POWER_FAULT)
17
with HB alarm (TA1 or TA2 or TA3)
AL1 and AL2 or (AL.HB or POWER_
18
FAULT) with HB alarm (TA1 or TA2 or
TA3)
19 AL.HB - HB alarm (TA2)
20 AL.HB - HB alarm (TA3)
22 AL.HB - HB alarm (TA1)
23 POWER_FAULT
24 IN2 - repetition of logic input INDIG2
25 IN3 repetition of logic input INDIG3
26 IN4 repetition of logic input INDIG4
FUSE_OPEN / SHORT_CIRCU-
27
IT_CURRENT
28 Overheat alarm
29 Communication error
30 Device not ready
Ou.P (control output) with fast cycle
64
time 0.1 ... 20.0 sec.
+ 32
for logic level denied in output
+ 128
to force output to zero
0
0
0
Zone 1
Zone 2
Zone 3
5
5
5
Zone 1
Zone 2
Zone 3
43