Auxiliary Inputs; Transmitter Supply - gefran 800P Installation And Operation Manual

Controller/programmer
Table of Contents

Advertisement

Function indicator:
Indicates modes of operation
MAN = OFF (Automatic control)
MAN = ON (Manual control)
AUX = ON (program in reset)
PRG = ON (program running)
Auto / Manual selection
Only active in level 1 menu
Press to increment (decrement) any numerical parameter •• Increment (decrement) speed is proportional to time key stays
pressed •• The operation is not cyclic: once the maximum (minimum) value of a field is reached, the value will not change
even if the key remains pressed.
• Serial line
Configurable serial
18
-
line isolated to 1500V
Tx
Passive current loop
17
+
(max. 1200 baud)
16
-
RS422/485 or RS232
Rx
(optional)
15
+
• Outputs
User configurable
-
19
generic output
Out2 (AL1)
- 5A/250Vac relay, cosj = 1
20
+
- 11Vdc logic, Rout = 220Ω
(6V/20mA)
-
21
Out1 (Main)
22
+
• Power Supply
Standard:
100...240Vac/Vdc
~
23
Optional:
PWR
20...27Vac/Vdc
~
24
50/60Hz

• Auxiliary inputs

Auxiliary input isolated
-
~
14
Current transformer
50mAac, 1,5Ω, 50/60Hz
Remote setpoint
~
+
13
0...20, 4...20mA, 5Ω
0...1V, 0...10V, > 1MΩ

• Transmitter supply

Transmitter supply
GND
isolated 1500V
11
10/24Vdc, max. 30mA short-
+ Vt
12
circuit protection
Line voltage and outputs
C
D
80215G_MHW_800P_07-2021_ENG
3 • DESCRIPTION OF FACEPLATE
"Raise" and "Lower" key
4 • CONNECTIONS
A (Data +)
B (Data -)
Tx
Out4 (AL3/
GND
Rx
RS485 2-wires
RS232
19
20
!
21
22
23
24
1500V
(alternative to IN2 digital
(*) terminal 11 if Out 4 is
5 • RECOMMENDED WIRING LAYOUT
Low level signals
B
A
User configurable
generic output
7
-
- 5A/250Vac relay, cosj=1
HB)
- 11Vdc logic,
(W1)
Rout = 220Ω (6V/20mA)
8
+
- analogue output isolated to 1500V
(0...10V, 0...20/4...20mA)
TOP
18
7
6
17
8
5
16
9
4
15
10
3
14
11
2
13
12
1
• Digital inputs / Out 5
Out 5 analogue (W2)
9
input)
Relay or Logic
7
Line voltage
A
Inputs
B
Serial
C
Relay outputs
D
Power supply
E
Logic/Analogue
outputs
Indication of output states
OUT 1 (Main); OUT 2 (AL 1);
OUT 3 (AL 2); OUT 4 (HB)
PV Display: Indication of process variable
Error Indication: LO, HI, Sbr, Err
LO = the value of process variable is < di LO_S
HI= the value of process variable is > di HI_S
Sbr = faulty sensor or input values higher than max. limits
Err = PT100 third wire opened for PT100, PTC or input values
lower than min. limits (i.e.: TC wrong connection)
SV display: Indication of setpoint
Function key:
Gives access to the various configuration phases •• Confirms
change of set parameters and browses next or previous
parameter (if Auto/Man key is pressed)
• Outputs
User configurable
generic output
- 5A/250Vac relay, cosj=1
- 11Vdc logic,
Rout = 220Ω (6V/20mA)
• Inputs
• Pt100 2-wires or PTC
Use wires
3
of adequate
diameter
2
(min. 1mm
)
2
PT100,
JPT100, PTC
1
• TC
Available thermocouples:
J, K, R, S, T, B, E, N,
Ni-Ni18Mo, L NiCr-CuNi
- Observe polarities
- For extensions, use the
correct compensating cable
for the type of TC used
• Linear (V)
Linear input in dc voltage
0...50mV, 10...50mV,
0...10V, 2...10V
Potentiometer 0...10V
• Linear (I)
Linear input in
dc current
0...20mA, 4...20mA
Digital input
+
isolated to 1500V
- NPN 24V, 4,5mA
- PNP 24V, 3,6mA
(12V, 3,6mA)
(*)
COM
(In alternative Out 5)
D
6
-
Out3 (AL2)
5
+
• Pt100 3-wires
3
2
T
T
1
-
2
1
+
2
-
1
+
4
2
-
1
+
9
IN2
10
IN1
11
COM
Low level signals
E
B
A
19

Advertisement

Table of Contents