Integrated Controller and Operator Panel Connections

Inputs, ports and signals

1
2
5
7
GF VEDO SL 35CT
N.
Description
1
Input power 24 Vdc ± 25%
2
CAN Port
3
Ethernet Port 10/100 Mbit/s
4
USB Port
5
SD Card Slot
6
RS232 Port
7
Insulated RS485 Port
8
Green "Link" LED
9
Yellow "Data" LED

Power

The Integrated Controller and Operator Panel must be con-
nected to a 24 Vdc power supply unit.
The same 24 Vdc power supply can feed several devices
(controller and CAN-IO modules).
Make sure that the current issued by the power supply is
higher than the total maximum current absorbed by all the
devices connected.
230 Vac
Figure 10 - GF_VEDO SL power
14
8
3
9
4
6
Figure 9 - GF_VEDO SL connector position
Connector / indicator
Pull-out polarised terminal block
DB9 M (D-sub 9 pin male)
RJ45
USB Type A
DB9 M (D-sub 9 pin male)
DB9 M (D-sub 9 pin male)
Permanently on signals that the
Ethernet connection is active
Flashing signals that data is being
transferred
24 Vdc
-
+
1
5
7
GF VEDO SL 70CT
GF VEDO SL V70CT
Note
optional
optional
optional
optional
A high-speed transfer could
make the yellow LED appear
permanently on
Considering that the device has no switch, it is necessary to
install one before it, with a protective fuse.
The switch has to be positioned in the immediate vicinity of
the device and be easy for the operator to reach.
For the 24 Vdc power supply, use a separate line from that
used for electromechanical power devices such as relays,
contactors, solenoids, etc.
If there are considerable changes in the mains voltage, use
a voltage stabiliser.
Near to high frequency generators or arc welders, use ade-
quate grid filters.
Connect the power cables to the power connector. Fit the
cylindrical nucleus in ferrite, supplied with the product, as
close as possible to the device to limit the susceptibility of
the device to electromagnetic disturbance (figure 11).
The 24 Vdc power cables must follow a separate route from
the power cables of the system or the machine.
80991C_MHW_GF_VEDO SL_09-2017_ENG