Troubleshooting - FULTON VSRT Series Installation, Operation And Maintenance Manual

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

SECTION 4
VSRT-IOM-2022-0728

Troubleshooting

Refer to table below for troubleshooting.
Problem
Cause
Power Supply
Ignition Electrodes
Transformer
Flame Safeguard Control
Ignition Failure
Faulty Air Switch
Gas Supply*
Loose Wire Connection
Power Supply
Gas Supply*
Ignition Electrodes
UV Scanner
Flame Failure
Flame Safeguard Control
Loose wire at fuel valve circuit
Contact open on air safety
switch
Scanner wiring reversed at
panel box
VSRT-9.5, 80-250 Air Filter
* For natural gas fired boilers. Refer to the test fire sheet for all other fuels.
Questions? Please Contact Your Local Manufacturer's Representative
MAINTENANCE & TROUBLESHOOTING
Troubleshooting Gas Fired Boilers
Remedy
Check fuse or circuit breaker. Reset or replace, as necessary.
Check electrodes for carbon buildup and clean if necessary.
Check for proper adjustment. Readjust if necessary. Check for
cracks in porcelain. If found, replace.
Check voltage between transformer leads at terminal block to
be sure transformer is being powered.
Check voltage between ignition terminal and neutral. Check
must be made before control locks out on safety. If no power,
replace control.
Use a volt meter in series with the air switch to check to see if
the switch is making (closing). Also check the adjustment of
the air switch setting. If both above do not work, check the
range of the air switch and measure the burner fan pressure at
the air pressure switch sensing port to make sure the air switch
is within range.
Check for gas pressure and for intermittent supply problems.
See Table 3 for appropriate gas pressures required at the head
of the train.
Check connections to all components.
Check fuse or circuit breaker. Reset or replace, as necessary.
Check for gas pressure and for intermittent supply problems.
See Table 3 for appropriate gas pressures required at the head
of the train.
Check electrodes for carbon buildup and clean if necessary.
Check for proper adjustment.
Readjust if necessary. Check for cracks in porcelain; if found,
replace.
Check for debris on flame scanner and clean as needed.
Check for proper location of detector.
Check voltage at terminal leading to main gas valve. If no
power, replace the control.
Tighten wiring connections.
Adjust to proper setting.
Change to correct terminals.
Inspect combustion air filter, replace if dirty.
4-13