FULTON VSRT Series Installation, Operation And Maintenance Manual page 15

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

SECTION 2
VSRT-IOM-2022-0728
Unit Size (BHP)
Maximum allowable working pressure
Boiler input (BTU/HR)
Boiler input (Natural gas); CU FT/HR
Boiler input (Propane); CU FT/HR
RATINGS* (Sea level to 3000 ft (914.4 m)
Boiler Output (BTU/HR)
Steam Output - Minimum Service
Capacity; LB/HR (KG/HR)
Net Effective Heating Service (SQ. FT)
Water Capacity (Operating); GAL.
Burner Turndown
Draft Requirements
Minimum Incoming Gas Pressure (PSIG)
Maximum incoming Gas Pressure (PSIG)
Weights (Approximate)
Dry Weight; LBS
Operating Weight; LBS
Shipping Weight; LBS
Flooded Weight; LBS
Electric Power Requirements
Voltage
FLA at Voltage noted above
Operating Amps at High Fire
Notes for Table 3
1. Steam output LB/HR: From 0 PSIG at 212°F (0 kg/cm² at 100°C).
2. All clearances are factory recommendations. Consult local
jurisdiction for exact code compliance.
3. Fulton recommends minimum clearance of 36" in front of
electrical panels.
4. Fulton recommends 36" clearance between inspection
openings of all boilers, 18" clearance of handholes, and 18" from
exhaust stack.
5. All dimensions inside ( ) denote reference dimensions.
6. All dimensions inside rectangles denote overall dimensions.
Questions? Please Contact Your Local Manufacturer's Representative
TABLE 3 - VSRT SPECIFICATIONS
9.5
10
15
100 PSI
150 PSI
150 PSI
150 PSI
388,815
400,000
600,000
800,000
385
400
600
156
160
240
318,051
335,000
503,000
670,000
328
345
518
(149)
(156)
(235)
36
54.5
54.5
25.75
102
102
8:1
4:1
6:1
3" W.C.
3" W.C.
3" W.C.
3" W.C.
13.8" W.C.
13.8" W.C.
13.8" W.C.
13.8" W.C.
1,700
2,650
2,650
1920
3,500
3,500
1850
2,900
2,900
2000
3,850
3,850
120/6/1
120/60/1
120/60/1
120/60/1
16 AMPS
27 AMPS
27 AMPS
27 AMPS
4 AMPS
10 AMPS
10 AMPS
10 AMPS
20
30
40
50
150 PSI
150 PSI
150 PSI
1,200,000 1,600,000 1,993,000 2,392,000 3,223,000 4,043,357 5,084,903
800
1,200
1,600
1,933
320
480
640
797
1,005,000 1,339,000 1,674,000 2,008,500 2,678,000 3,347,900 4,184,875
690
1,035
1,380
1,725
(313)
(470)
(626)
(782)
65
65
116
116
112
112
333
333
4:1
6:1
6:1
8:1
-0.25" W.C. to +1.50" W.C.
3" W.C.
3" W.C.
3" W.C.
13.8" W.C.
13.8" W.C.
13.8" W.C.
3,100
3,100
5,100
5,100
4,100
4,100
7,864
7,864
3,400
3,400
6,000
6,000
4,400
4,400
8,600
8,600
240/60/1
480/60/3
480/60/3
30 AMPS
17 AMPS
17 AMPS
15 AMPS
15 AMPS
15 AMPS
7. We reserve the right to change specifications and/or
dimensions. All information is subject to change based on
addition of any optional equipment and/or accessories. Please
consult the factory for project specific estimates if additional
options or accessories are required.
8. Local codes can supercede Fulton recommended clearance.
9. The VSRT-10 is available as an 8.5 HP model.
10. The VSRT-9.5 is only available at 100 PSI MAWP Design and 80
PSI Trim
INSTALLATION
60
80
100
150 PSI
150 PSI
150 PSI
150 PSI
2,392
3,223
4,043
5,085
957
-
-
2,070
2760
3450
(939)
(1252)
(1565)
(1956)
116
140
203
333
393
898
10:1
10:1
10:1
3" W.C.
4" W.C.
13" W.C.
13" W.C.
13.8" W.C
13.8" W.C
5 PSIG
5 PSIG
5,100
5,800
11,485
11,485
7,864
9,080
18,975
18,975
6,000
6,700
11,800
11,800
8,600
9,710
19,925
19,925
480/60/3
480/60/3
480/60/3
480/60/3
17 AMPS
16 AMPS
24 AMPS
24 AMPS
15 AMPS
8.8 AMPS
8.2 AMPS
AMPS
125
250
150 PSI
9,822,500
9,823
-
-
8,368,750
4313
8625
(3912)
203
539.5
898
1663
10:1
10:1
13"W.C.
5 PSIG
22,500
36,369
23,000
38,988
480/60/3
36 AMPS
11.7
-
2-5

Advertisement

Table of Contents
loading

Table of Contents