FULTON VSRT Series Installation, Operation And Maintenance Manual page 105

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

SECTION 5
VSRT-IOM-2022-0728
BLOW DOWN TANK
VENT CONNECTION
DRAIN OUTLET RUN FULL SIZE AND IN PROPER MATERIAL TO SUITABLE DRAIN
FEED WATER TANK
PUMP QUANTITY
PUMP MAKE & MODEL
PUMP MOTOR HORSEPOWER
PUMP MOTOR VOLTAGE
PUMP MOTOR FULL LOAD AMPERAGE
PUMP MOTOR EFFICIENCY
PUMP POWER FACTOR
PUMP ROTATION IS CORRECT
PUMP IS BLED AND PRIMED
ISOLATION VALVE IS INSTALLED, PUMP IS SERVICEABLE
PUMP HAS RECIRCULATION LINE FOR DEAD HEAD PROTECTION IF CONTINUOUS RUN
RETURN TANK
SIZE OF RETURN TANK
MAKEUP WATER SUPPLY PRESSURE
VENT CONNECTION
LEVEL CONTROLS ARE INSTALLED CORRECTLY
PREHEAT KIT INSTALLED & STEAM PRESSURE SUPPLIED
DEAERATOR TANK
VENT CONNECTION
SAFETY VALVE IS PRESENT AND SIZED PROPERLY
SAFETY VALVE IS PIPED TO SAFE LOCATION
SAFETY VALVE IS PIPED TO SAFE LOCATION
SAFETY VALVE HAS A MEANS TO PREVENT CONDENSATE FROM RETURNING TO THE VALVE
VENT CONNECTION HAS A MEANS TO PREVENT CONDENSATE FROM RETURNING TO THE VALVE
Questions? Please Contact Your Local Manufacturer's Representative
START-UP: INSTALLATION & OPERATION REPORT
FREE TO ATMOSPHERE
TERMINATED TO A SAFE AREA
SAME SIZE AS TANK OUTLET
COOLING KIT INSTALLED
FREE TO ATMOSPHERE
TERMINATED TO SAFE AREA
SAME SIZE AS TANK OUTLET
FREE TO ATMOSPHERE
PREVENTS CONTAMINATION
VENTED TO A SAFE LOCATION
SAME SIZE AS TANK OUTLET
SERVICE DOCUMENTS
FOR FULTON STEAM BOILERS
PUMP 1
PUMP 2
PAGE 2 OF 9