FULTON VSRT Series Installation, Operation And Maintenance Manual page 61

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

SECTION 2
VSRT-IOM-2022-0728
EXHAUST PIPE
WALL PENETRATION
48 IN. / 122 CM.
(MINIMUM)
Questions? Please Contact Your Local Manufacturer's Representative
APPROVED EXHAUST
VENT MATERIAL
AIR INTAKE & EXHAUST PIPES WALL PENETRATION CLEARANCES
10 FEET
(MINIMUM)
EXHAUST PIPING
AIR INTAKE
WALL PENETRATION
WIND DIRECTION
FIGURE 31- SIDE WALL PENETRATION DETAILS FOR VSRT 9.5-125 BHP
DO NOT PLACE INSULATION IN
REQUIRED AIR SPACE CLEARANCE
RISE TO RUN: 1/4" PER FOOT
CAUTION:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
LOCATE INTAKE
RECIRCULATION DURING DIFFERENT WIND CONDITIONS
UPWIND OF
NOTE:
MAINTAIN MINIMUM 9"/22.86 CM AIR SPACE
CLEARANCES TO COMBUSTABLES, WIRES AND INSULATION
NOTE:
1.) When using horizontal runs follow a 1/4" per foot rise to run ratio
2.) Maintain minimum 9" / 22.86 cm air space clearances to combustables,
wires and insulation
3.) Install support straps at 5 FT / 152 CM horizontal intervals and at elbows
INSTALLATION
WALL
WALL TERMINATION
( WITH SCREEN )
4 FT / 122 CM ( MINIMUM )
BETWEEN INLET & EXHAUST
OPENING ( SEE BELOW )
BAND SUPPORT
AIR INTAKE AND EXHAUST
COLLAR
TERMINATION SHOULD BE
(TYP EACH SIDE)
SEPERATED AS FAR AS POSSIBLE
TO PREVENT FLUE GAS
RECIRCULATION DURING
DIFFERENT WIND CONDITIONS.
6 IN / 15 CM
MIN
OPENING 1 FT / 30 CM ( MIN )
ABOVE NORMALLY EXPECTED
90° ELBOW
SNOW ACCUMULATION LEVEL
SCREENED AIR INLET
2-51