FULTON VSRT Series Installation, Operation And Maintenance Manual page 83

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

SECTION 3
VSRT-IOM-2022-0728
Parameter
Par. No.
602
Actuator's direction of rotation
Index 0 = fuel, Index 1 = air
0 = counterclockwise
1 = clockwise
606
Tolerance limit of position monitoring
641
Control of speed standardization of VSD
642
Standardized speed
Index 0 = uC1
Index 1 = uC2
645
Configuration of analog output
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0/2...10 V
700
Error History
701
Error history: 701-725.01. Code
.
Error history: 701-725.02. Diagnostic Code
.
Error history: 701-725.03. Error class
.
Error history: 701-725.04. Phase
.
Error history: 701-725.05. Startup counter
725
Error history: 701-725.06. Load
900
Process Data
903
Current output
Index 0 = fuel
Index 1 = air
922
Incremental position of actuators
Index 0 = fuel
Index 1 = air
935
Absolute speed
936
Standardized speed
942
Active load source
947
Result of contact sensing (bit-coded)
950
Required relay state (bit-coded)
954
Intensity of flame
960
Actual flow rate
961
Status for external modules and display
981
Error storage: Code
982
Error storage: Diagnostic code
992
Error flags
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and
safety. No Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note: Customer settings should be recorded in the Customer column for reference.
Questions? Please Contact Your Local Manufacturer's Representative
TABLE 8 - STEAM PROGRAM FOR SIEMENS LMV3*
Min Value
Max Value
0
1
0.5
2.5
-25
1
650
6500
0
2
0
255
0
255
0
6
0
255
0
99999999
0 %
100 %
0 %
100 %
-50
150
0
65535
-200 %
200 %
0
255
0
255
0
255
0 %
100 %
0
65525
0
255
0
255
0
255
0
0xFFFFFFFF
OPERATION
Fulton Setting
Customer
0
0
1.7
0
Undefined
0
0
0
0
3-19