FULTON VSRT Series Installation, Operation And Maintenance Manual page 79

Vertical spiral-rib tubeless boiler
Table of Contents

Advertisement

SECTION 3
VSRT-IOM-2022-0728
2. Gas valve will shut. The blower/fan may increase speed
briefly as the flow of gas is cut off. The blower/fan will
ramp to high-fire speed/rpm, and continue to run there
for a 15-second post purge.
Parameter
Par. No.
000
Internal Parameters
41
Password
100
General
102
Identification Date
103
Identification Number
104
Pre-selected parameter set : Code
105
Pre-selected parameter set : Vers.
107
Software version
108
Software variant
113
Burner identification
121
Manual output
Undefined = automatic mode
125
Main frequency
0 = 50 hz
1 = 60 hz
126
Display brightness
127
Timeout for menu operation
128
Fuel meter: pulse valency [pulses per volumetric
flow unit]
130
Delete display of error history: to delete the
display, set to 1 then to 2
141
Operating mode BACS
0 = off
1 = Modbus
2 = reserved
142
Setback time in the event of communication
breakdown
143
Reserved
144
Reserved
145
Device address for Modbus
146
Baud rate for Modbus
0 = 9600
1 = 19200
147
Parity for Modbus
0 = none
1 = odd
2 = even
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note: Customer settings should be recorded in the Customer column for reference.
Questions? Please Contact Your Local Manufacturer's Representative
TABLE 8 - STEAM PROGRAM FOR SIEMENS LMV3*
Min Value
Max Value
0
65535
0
255
0
65535
0
255
0
0xFFFF
0
0xFFFF
0
255
0
99999999
0%
100%
0
1
0%
100%
10 min
120 min
0
400
-5
2
0
2
0 s
7200 s
1
8
10 s
60 s
1
247
0
1
0
2
OPERATION
Fulton Setting
Customer
NB/SN
9
V.01.01
V 01.80
1
Undefined
1
100%
30 min
0
0
1
1 s
1
30 s
2
1
0
3-15