Guide when performing any changes on the unit flame programmer.
1. Press and hold the F and A buttons simultaneously. You will be prompted
for your password (####).
NOTE:
#### is the last four digits of the national board number.
2. Enter your password and press the "Enter" button.
3. Using the "–" button, scroll to parameter level 100.
4. To enter into a parameter level and start programming, press the enter
button.
5. Use the "+" and "-" buttons to scroll through the parameters.
6. Press the enter button to enter the parameter. The current value will start
flashing.
7. Use the "–" button to decrease the value or "+" button to increase the value.
8. Once the desired value has been set, press the "Enter" button. The number
will stop flashing.
9. Press the "–" and "+" buttons together to back out of the parameter level
when finished.
10. Press the "–" or "+" buttons to scroll to the next section of the program.
11. Repeat this process until all parameters have been reviewed and set.
12. Once the parameters have been programmed, back out to the front screen
by pressing the – and + buttons together.