App 408 Customer PET controller installation guide & user's manual
Page 18
2.3 Additional software features
2.3.1 Micro interruption of the power supply
The controller is equipped with a device that detects a micro interruption of the
power supply. Every zero crossing of the 24VAC mains is detected. When 2
consecutive cycles or a power failure of 40ms is detected, the controller will
automatically stop the machine. At the same time, all relays are released and
3 horizontal dashes are displayed on the LED display. By stopping the
machine during a micro interruption of the power supply, sparks on the relay
contacts are avoided which will extend the relay lifetime.
2.4 Menu structure – quick reference
Basic menu
Error log menu
Timer menu
App 408C
Function
Date & time
Ready to start
Standby
Starting busy
Offload
On load 50%
Stop busy
Blowing down
Warning and alarms
Logged error Nr. 1: error type + date & time
Logged error Nr. 2: error type + date & time
Logged error Nr. 3: error type + date & time
Logged error Nr. 4: error type + date & time
Logged error Nr. 5: error type + date & time
Logged error Nr. 6: error type + date & time
Logged error Nr. 7: error type + date & time
Logged error Nr. 8: error type + date & time
Logged error Nr. 9: error type + date & time
Logged error Nr. 10: error type + date & time
Total running hours
Total running hours in half load
Total running hours in full load
rd
No of times the 3
stage pressure has cycled
rd
past the low 3
stage pressure (15bar)
Remaining hours before service is required
Default setting
40ms
Table 19
High pressure H
High temperature HH
Air filter blocked
Motor overload
Motor over temperature
Power failure
etc.