Options:
The parameter is used to specify how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the upper temperature value is reached.
Typical values for summer compensation are:
20°C: lower outside temperature value
■
32°C: upper outside temperature value
■
0 K: lower setpoint offset
■
4 K: upper setpoint offset
■
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".