Temperature Reading - Monitoring Time For Temperature Reading; Temperature Reading - Operating Mode For Fault - Busch-Jaeger Busch-SmartTouch ST/U10.1.11-811 Product Manual

Table of Contents

Advertisement

Options:
The parameter is used to specify whether parameter "Monitoring time of temperature reading" is
available.
10.24.114
Temperature reading — Monitoring time for temperature reading
Options:
If no temperature is read within the parameterised time period, the device switches to error
mode. It transmits a telegram to the bus via the "Actual temperature error" and applies the
operating mode and control value for error.
Notice
This parameter is only available when parameter "Monitoring of temperature
reading" is activated.
10.24.115
Temperature reading — Operating mode for fault
Options:
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently specify the heating/cooling operating type. As a result, the operating type
best suited to protecting the building will be selected.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
Product manual 2CKA001473B5342
KNX control elements and application parameters
Deactivated
Activated
Setting option between 00:01:00 - 18:12:15
Cooling
Heating
Application "Internal RTC"
│267

Advertisement

Table of Contents
loading

Table of Contents