The parameter is used to specify whether the following parameters are available for the
"Temperature limit of additional cooling stage".
–
Setpoint temperature
–
Hysteresis
–
Integral component of PI controller
10.24.128
Temperature limiter - Setpoint temperature of cooling / additional cooling stage
Options:
The parameter is used to specify the value of the setpoint temperature for "Cooling" or the
"Additional cooling stage".
10.24.129
Temperature limiter - Hysteresis
Options:
The hysteresis specifies the fluctuation range of the controller around the setpoint value. The
lower switching point is located at "Setpoint value minus hysteresis" and the upper point is at
"Setpoint value plus hysteresis".
Notice
This parameter is only available when one or several of the following parameters
are activated.
"Temperature limit heating"
"Temperature limit additional heating stage"
"Temperature limit cooling"
Temperature limit additional cooling stage
10.24.130
Temperature limiter - Integral component of PI controller
Options:
The parameter is used to specify whether the integral component of the PI controller is retained
or reset.
Product manual 2CKA001473B5342
KNX control elements and application parameters
Setting option from 1 - 30
Setting option between 0.5 - 5
Keep
Reset
Application "Internal RTC"