ICP DAS USA I-8014W User Manual page 89

250 ks/s, 16-bit, 8-channel differential/16-channel single-ended analog input module
Table of Contents

Advertisement

Tips & Warnings
1. A battery output could provide a stable enough signal.
2. A 125 Ohm resistance is required when measuring current input.
3. In voltage measurement with differential input type, if the result is
not stable as the input signal, it is recommended to wire Vn- and
AGND (analog ground pin) additional to enhance the accuracy.
When measuring current input, it is no use to enhance to
accuracy.
Step2. Launch pac_i8014W_Utility.exe
Step3: Read the information in I-8014W.
a. Form the I-8014W slot index drop-down list, select the slot in which the
I-8014W is plugged.
b. Click the Basic Information tag.
The Basic Information page includes:
● the version of 8014W.lib, primary FPGA firmware (Firmware 1),
secondary FPGA firmware (Firmware 2)
● the position of single-ended/ differential jumper set
● the gain and offset values for each input type
I-8014W API User Manual, v1.0.1, June 2011
Copyright © 2011 ICP DAS Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com
89

Advertisement

Table of Contents
loading