ICP DAS USA I-8014W User Manual page 29

250 ks/s, 16-bit, 8-channel differential/16-channel single-ended analog input module
Table of Contents

Advertisement

To calibrate the I-8014W on WinCE and WES unit
Step1. Refer to
Jumper setting, page
make sure the Differential / Single
Ended select jumper is in differential
position.
Step2. Connect your calibration source to
channel 0 of I-8014W by differential
wiring.
Step3. Plug the I-8014W into the slot of
controller and turn on the controller.
Step4. Launch
pac_i8014W_Calibration.exe on
controller.
(In the c# demos for I-8014W, see
Demo Programs Location, page 12 and
Tips & Warnings
Only channel 0 is valid to perform calibration
I-8014W API User Manual, v 1.0.1, September 2011
Copyright © 2011 ICP DAS Co., Ltd. All Rights Reserved.
8,
13)