Step8. Click the Step1. Set point 1 tab, enter the value read by meter (ex. 8.0), and
click Set as Calibration Point 1.
Step9. Make calibration source output the other value (ex. - 8V)
Step10. Click the Step2. Set point 2 tab, enter the value read by meter (ex. - 8.0),
and click Set as Calibration Point 2.
I-8014W API User Manual, v 1.0.1, September 2011