YASKAWA Solectria PVI 25TL-208 Installation And Operation Manual page 78

Commercial 1000vdc string inverters
Hide thumbs Also See for Solectria PVI 25TL-208:
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
PARAMETER NAME
GRIDVOLTMAX1(%)
VOLTMAXTRIPTIME1(S)
GRIDVOLTMAX2(%)
VOLTMAXTRIPTIME2(S)
GRIDVOLTMAX3(%)
VOLTMAXTRIPTIME3(S)
GRIDVOLTMIN1 (%)
VOLTMINTRIPTIME1(S)
GRIDVOLTMIN2 (%)
VOLTMINTRIPTIME2(S)
GRIDVOLTMIN3(%)
VOLTMINTRIPTIME3(S)
Table 6-2 Grid Frequency Protection
GRID FREQUENCY PROTECTION
DOCR-071030-A (10/7/2022)
DESCRIPTION
MIN
Level 1 Max.
100.00
grid voltage
Level 1 Max.
0.00
grid trip
voltage
Level 2 Max.
100.00
grid voltage
Level 2 Max.
0.00
grid trip
voltage
Level 3 Max.
100.00
grid voltage
Level 3 Max.
0.00
grid trip
voltage
Level 1 Min.
30.00
Grid voltage
Level 1 Min.
0.00
grid trip
voltage
Level 2 Min.
30.00
Grid voltage
Level 2 Min.
0.00
grid trip
voltage
Level 3 Min.
30.00
Grid voltage
Level 3 Min.
0.00
grid trip
voltage
IEEE 1547
DEFAULT
MAX
110.00
135.00
1.00
655.00
120.00
135.00
0.16
655.00
120.00
135.00
0.16
655.00
88.00
100.00
2.00
655.00
60.00
100.00
1.00
655.00
45.00
100.00
0.16
655.00
SETTING RANGE
IEEE 1547
RULE 21
MIN
DEFAULT
100.00
110.00
0.00
12.50
120.00
100.00
0.00
0.16
100.00
120.00
0.00
0.16
30.00
88.00
0.00
20.50
30.00
70.00
0.00
10.50
30.00
50.00
0.15
0.00
RULE 21
Page 78 of 131
MAX
135.00
655.00
135.00
655.00
135.00
655.00
100.00
655.00
100.00
655.00
100.00
655.00