YASKAWA Solectria PVI 25TL-208 Installation And Operation Manual page 70

Commercial 1000vdc string inverters
Hide thumbs Also See for Solectria PVI 25TL-208:
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
c.
The default grid standard is IEEE 1547. If a different standard is needed please go to "Menu
Functions" section for further instructions on how to change it. Available grid standards are shown in
Figure 5-2.
Please check with your local electricity provider before selecting the grid standard. If the inverter is operated
with a wrong grid standard, the electricity provider may cancel the interconnection agreement. Putting the
inverter into operation before the overall system complies with the national rules and safety regulation of the
application is not permitted.
Figure 5-2- Select Grid Standard; ML-Molokai/Lanai; OHM- O`ahu, Maui, and Hawai`i
 Setting the Time. From the previous menu, press ESC to return to the System Parameters menu. Select
Time and press ENT. Scroll up/down to select the numerical value, then press ENT to go to next option.
e.g.: Year to Month, press ESC to go to last option. e.g.: Month to Year. Finally Press the ENT key to
confirm the setting. (Press the "up" arrow more than 1 second to go to last position of the number when
setting the parameters. e.g: 2008 to 2008. Press the "down" arrow more than 1 second to go to the next
position of the number when setting the parameters. e.g: 2008 to 2008.)
 The factory default working mode of the DC input connection and MPP Tracker is set for Independent and
shall only be configured as Independent. Parallel is not an option for this inverter line.
 Neutral Line Setting. From the previous menu, press ESC to return to the System Parameters menu.
Select Neutral Line Setting and press ENT. Use the arrow keys to highlight "Yes" or "No" in regard to
whether a neutral conductor is present. Press ENT. This setting will allow the inverter to display L-N
voltages on the LCD. It will not affect the operation of the inverter.
DOCR-071030-A (10/7/2022)
INFO ✔
Grid Connection Rule
IEEE1547
CA Rule-21/UL 1741 SA
HECO-HM
HECO-ML
NONE
Page 70 of 131