Once this MPPT scan function is activated thru the LCD, it will search the maximum power point at a
voltage step of 5V in the MPPT range for full load, and get the maximum power point.
In this interface you can change the Protect parameters of grid voltage, frequency and recovery, etc., as shown in
Figure 6-7. You can't enable/disable the function. The protect parameters are shown in Table 6-1.
There are 7 pages of parameters displayed. Switching between parameters is done by pressing
. Then press ENT to select it, change the parameter value by pressing
the parameter to inverter. The LCD will display new parameters if the setting is successful. Otherwise the old
parameters will display on the LCD.
Table 6-1 Protection Submenu Parameters with lower limit, default, and upper limit settings (IEEE 1547-2018 and Rule 21) for
GRID VOLTAGE PROTECTION
DOCR-071030-A (10/7/2022)
Protect Parameters
Figure 6-7 Protection Parameters Setting
the PVI 50/60TL-480 and PVI 25TL-208
INFO ✔
SETTING RANGE
then press ENT to send