Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
CONNECTION POINT
AC OUTPUT TERMINAL BLOCK
INTERNAL GROUNDING BAR
EXTERNAL GROUNDING POINT
The AC Terminals are 90°C rated. The maximum acceptable conductor size that may be terminated to the AC
output terminal is restricted based on the compression lug maximum dimensions shown in Figure 3-36.
DOCR-071030-A (10/7/2022)
Figure 3-34 AC Output and Ground Cable Connection
Table 3-11 Torque and Conductor Specifications
CONDUCTOR RANGE
L1/L2/L3:
6
-3/0AWG(75/90°C
6 - 3/0AWG
(90°C
Neutral:
8 - 3/0AWG
(75/90°C
6-4 AWG (CU)
6-4 AWG (CU)
14.25 N-m (126 in-lbs)
Cu)
Al)
Cu/Al)
5.65 N-m (50 in-lbs)
5.65 N-m (50 in-lbs)
TORQUE VALUE