Appendix A: TV-VVTZC-E2 Points/Properties
WS Battery Strength % — Displays charge strength indicated on the wireless space
temperature sensor. If there are multiple wireless sensors, it displays the lowest value.
WS Signal Strength % — Displays radio signal strength of the wireless space temperature
sensor. If there are multiple wireless sensors, it displays the lowest value.
Rnet Sensed Occupancy – Displays occupancy status detected by wireless infrared
motion sensor.
ZS model to show on graphic – Select the ZS model, from the drop-down list, that you
want to display on the graphic.
WS model to show on graphic – Select the wireless model, from the drop-down list, that
you want to display on the graphic.
Net Space Temp to show on graphic — Select the type of sensor to display on graphic.
System Space Temperature – The current value of the controlling space temperature
received over the network from another source. -999 indicates no value has been
received and it will not be used.
System Setpoint Adjustment – The space temperature setpoint adjustment value
received over the network.
System Space RH – The relative humidity received over the network. -999 indicates no
value has been received and it will not be used.
System Space AQ – The indoor air quality received over the network. -999 indicates no
value has been received and it will not be used.
System Cool Demand Level– The value received over the network and used by the
demand limiting function to expand the cooling setpoint.
System Heat Demand Level– The value received over the network and used by the
demand limiting function to expand the heating setpoint.
System Outdoor Air Temperature – The OAT received over the network.
System Occupancy – The status of the System Occupancy network point.
TruVu™ VVTZC-E2
Installation and Start-up Guide
120
R:
_%
R:
_%
R:
Off/On
D:
ZS Pro model
R:
None
ZS Pro model
ZS Base model
ZS Plus model
D:
WS Plus model
R:
WS Base model
WS Plus model
WS Pro model
D:
Equipment Touch
R:
Network Temp
Equipment Touch
R:
-50 to 150°F
(-45.5 to 65.5°C)
R:
-5 to 5 °F
(-2.7 to 2.7 °C)
R:
2 to 100%
R:
300 to 9999 ppm
R:
0 to 3
R:
0 to 3
R:
-50 to 150°F
(-45.5 to 65.5°C)
D:
Unoccupied
R:
Unoccupied/Occupied