Wiring inputs and outputs

See Appendix A (page 29) to print a blank wire list.

Input wiring specifications

Input
0–5 Vdc
0–10 Vdc
0–20 mA
Thermistor
Dry contact
Pulse counter
TLO
RTD
SPT sensors

Inputs - UC Open XP

The UC Open XP has 12 inputs that accept the signal types described below.
These
inputs...
All
All
UI-1, UI-2
UC Open XP/UC Open XP IO
Maximum length
Minimum gauge
500 feet
22 AWG
(152 meters)
1000 feet
22 AWG
(305 meters)
500 feet
22 AWG
(152 meters)
100 feet
22 AWG
(30 meters)
500 feet
18 AWG
(152 meters)
Support this
signal type...
Description
Thermistor
Precon type 2 (10 kOhm at 77°F). Input voltages should be from
0.489 Vdc to 3.825 Vdc for thermistors.
RTD
0–10 Vdc
4-20 mA
Dry contact
A 5 Vdc wetting voltage detects contact position, resulting in a 0.5
mA maximum sense current when the contacts are closed.
0–20 mA
The input impedance of the UC Open XP is approximately 1 MOhm.
Pulse input
Shielding
100 feet Unshielded
100 - 500 feet Shielded
100 feet Unshielded
100 - 1000 feet Shielded
100 feet Unshielded
100 - 500 feet Shielded
Shielded
Unshielded
13