Maintenance - Carrier TruVu VVTZC-E2 Installation And Startup Manual

Table of Contents

Advertisement

Maintenance

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Unit
Occupancy Status – The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
Temp Compensated Start or Learning Adaptive Start – Indicates the type of optimal
start (if any) that is configured and whether the algorithm is active or inactive.
Space Temp Source – The source of the controlling space temperature value.
Options:
Sensor Failure – No valid space temperature or sensor status = failed.
SPT Sensor – An SPT sensor is connected to the controller's Rnet port.
T55/56 – A T55, T56, or T59 sensor is connected to the controller's I/O terminals.
Network – A network temperature sensor is bound to the controller's space
temperature AV.
Airside Linkage – The space temperature from a linked terminal.
Locked Value – The controller's space temperature input has been manually locked at a
value.
ZS Sensor – A ZS sensor is connected to the controller's Rnet port.
Setpoint Adjustment – The amount that a user has adjusted the setpoints on a zone
sensor.
Effective Heat Setpoint – The current heating setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from Optimal Start to Demand
Limit.
Effective Cool Setpoint – The current cooling setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from Optimal Start to Demand
Limit.
Relative Humidity Source – The source of the relative humidity value.
IAQ Source – The source of the indoor air quality value.
Outdoor Air Temperature Source – The source of the outdoor air temperature.
Cooling Demand Level – The system cool demand level received over the network.
TruVu™ VVTZC-E2
Installation and Start-up Guide
Properties
Control Program
>
121
Appendix A: TV-VVTZC-E2 Points/Properties
Maintenance
>
Default/Range
R:
Unoccupied/Occupied
R:
Inactive/Active
R:
Sensor Failure
SPT Sensor
T55/T56
Network
Airside Linkage
Locked Value
ZS Sensor
R:
-20 to 20 °F
(-11.1 to 11.1 °C)
R:
_°F/C
R:
_°F/C
R:
N/A
Local
Network
Linkage
Locked Value
ZS Sensor
R:
N/A
Local
Network
Linkage
Locked Value
ZS Sensor
R:
N/A
Local
Network
Linkage
Locked Value
R:
0 to 3