Carrier TruVu VVTZC-E2 Installation And Startup Manual page 134

Table of Contents

Advertisement

Appendix A: TV-VVTZC-E2 Points/Properties
Point Name/Description
BACnet configuration:
Network Visible - Must be enabled for other BACnet objects to read or write to this
point, and for this point to generate alarms.
Object Name - Do not change.
CO2 Sensor – The current voltage of the controller's IN-01 input.
RH Sensor – The current voltage of the controller's IN-01 input.
T55 Zone Temp – The current value of the controller's IN-02 space temperature sensor
input.
SAT Sensor – The current value of the controller's IN-03 supply air temperature sensor
input.
Smart Valve Pos – The value provided by the controller's Smart Valve.
LUX – The value provided by the controller's ZS sensor to indicate lighting level.
WS Battery Strength % — Displays charge strength indicated on the wireless space
temperature sensor. If there are multiple wireless sensors, it displays the lowest value.
WS Signal Strength % — Displays radio signal strength of the wireless space
temperature sensor. If there are multiple wireless sensors, it displays the lowest value.
Zone Humidity – The value provided by the controller's ZS or wireless sensor (if
present). See details below.
Zone Temp – The value provided by the controller's ZS or wireless sensor (if present).
ZS Zone CO2 - IAQ/CO2 signal received from CO2-enabled ZS Sensor(s).
ZS/WS Sensors
The following properties apply to the ZS or wireless Standard, ZS or wireless Plus,
and ZS or wireless Pro only. Sensor configurations on the microblock's Properties
> Details tab are listed below for:
Zone Humidity
Zone Temp
ZS Zone CO2
Default Value – The value that outputs when communication of all enabled
sensors fails or during sensor startup. The default value is used for each sensor's
corrected value in the i-Vu® system when the Valid? output is False (Off).
Sensor Configuration table
(Index) Area – The Index number corresponds to the sensors defined in
Configuration > Service Configuration > Sensor Binder. (Ctrl+click the
property name. See Service Configuration (page 114).)
Use – Check Enable for each sensor that you want to include in the
combination algorithm used to determine the output value.
TruVu™ VVTZC-E2
Installation and Start-up Guide
128
Default/Range
D:
Enabled
D:
zone_temp
R:
0 to 5 Vdc
R:
0 to 5 Vdc
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
-56 to 140°F
(-48.9 to 60°C)
R:
_%
R:
0 to 1020 lx
R:
_%
R:
_%
R:
_%
R:
_F°
R:
_ppm
D:
-999
R:
-999 to 999
D:
(1) Main ZS/WS Sensor
R:
(1) to (5)
D:
Enabled index (1)
R:
checked or unchecked
©2022 Carrier.
All rights reserved.