Carrier TruVu VVTZC-E2 Installation And Startup Manual page 125

Table of Contents

Advertisement

Zone Humidity - Configure additional ZS or wireless humidity sensors used on the TV-
VVTZC-E2.
Use - Check to include ZS or wireless sensors' value in the Combined Algorithm
(Maximum is the default).
Raw Value - Displays sensed humidity for each ZS or wireless humidity sensor's
address
Calibration - If needed, enter value to adjust the Corrected Value from the Raw
Value, in order to calibrate an individual ZS or wireless sensor's sensed value.
Combination Algorithm - Use Average, Maximum, or Minimum ZS or wireless
humidity to calculate the Corrected Value for humidity control.
ZS Zone CO2 - Configure additional ZS CO
Use - Check to include ZS sensors' value in the Combined Algorithm (Maximum is
the default).
Raw Value -Displays sensed CO
Calibration - If needed, enter value to adjust the Corrected Value from the Raw
Value, in order to calibrate an individual ZS sensor's sensed value.
Combination Algorithm - Use Average, Maximum, or Minimum ZS CO
the Corrected Value for CO
TruVu™ VVTZC-E2
Installation and Start-up Guide
sensors used on the TV-VVTZC-E2.
2
for each ZS CO
sensor's address
2
2
control.
2
Appendix A: TV-VVTZC-E2 Points/Properties
2
to calculate
119
D:
(Index) Area - (1) Main
Sensor
Use - unchecked
Calibration - 0
Combination Algorithm -
Maximum
Input Smoothing - None
Show on Sensors -
Calculated Value
Display Resolution - 1
COV Increment - 1
D:
(Index) Area - (1) Main ZS
Sensor
Use - unchecked
Calibration - 0
Combination Algorithm -
Maximum
Input Smoothing -
Medium
Show on Sensors -
Calculated Value
Display Resolution - 1
COV Increment - 10
©2022 Carrier.
All rights reserved.