Service Configuration - Carrier TruVu VVTZC-E2 Installation And Startup Manual

Table of Contents

Advertisement

Appendix A: TV-VVTZC-E2 Points/Properties
Point Name/Description
Dirty Filter Alarm – If set to display, shows the alarm indicator on the communicating
zone sensors, if a Filter alarm is active.
Space High Humidity Alarm – If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the Space Relative Humidity alarm is
active.
Space High CO2 Alarm – If set to display, shows the alarm indicator on the
communicating zone sensors with display if the Indoor Air Quality Alarm is in alarm.
Maintenance Displayed on ZS Sensor
Linkage Fault – If set to display, shows the maintenance indicator on the ZS Pro sensor
if the Airside Linkage is in a Fault condition.
Net OAT Fault – If set to display, shows the maintenance indicator on the ZS Pro sensor
if the Network Outside Air is not valid.
SPT Sensor Fault – If set to display, shows the maintenance indicator on the ZS Pro
sensor if the space temperature sensor is not valid.

Service Configuration

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Terminal Type – The type of zone terminal that the controller is installed on.
Damper Size (dia.) – Used by the VVT Master to calculate the weighted average
demand. If the zone damper is round, enter its diameter. If rectangular, enter 0.
Damper Area (area) – Used by the VVT Master to calculate the weighted average
demand. If the damper is rectangular, enter its area (width x height). If the damper is
round, enter 0.
Terminal Fan Airflow – Enter the terminal fan airflow in cfm (liters/second). Used in
performance calculations only. Available only on fan-enabled terminal box.
TruVu™ VVTZC-E2
Installation and Start-up Guide
Properties
Control Program
>
114
Default/Range
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
D:
Ignore
R:
Ignore/Display
Configuration
Service Configuration
>
>
Default/Range
D:
Single Duct
R:
Single Duct
Parallel
Series Fan
D:
6.00 in. (15.2 cm)
R:
0 to 100.00 in./cm
D:
0 sq.in. (cm. sq.)
R:
0 to 9999 sq.in.
(cm. sq.)
D:
1000 cfm
(472 liters/second)
R:
0 to 99999 cfm
(liters/second)
©2022 Carrier.